Heatreat 502 Heatreat 502 is a blended formulation of tannins, alkalis and polymers for preventing corrosion, scaling and organic fouling in hat water and chilled water systems. Appearance Dark Brown Fluid ph as Supplied 9.7 Specific Gravity 1.14
Treatment for steam boilers Heatreat 502 is dosed so as to maintain the D.M. value (tannin index) and the ph of the boiler water within set limits. Usually the D.M. value of 12 - 16 and a ph greater than 10 For D.M. value a simple test using reagents in tablet form is available. For ph, indicator test papers are suitable.
Dosage Requirements The initial dose is normally 3litre/1 cubic metre
Metric measurements 3 litres per 1000 litres 1 litre per 333 litres 500ml per 167 litres 100 ml per 33 litres 10 ml per 3.3 litres 1 ml per 330 ml
Imperial measurements 24 pints per 1000 gallons 12 pints per 500 gallons 6 pints per 250 gallons 3 pints per 125 gallons 1 pint per 40 gallons 10 fl. oz. per 20 gallons 5 fl. oz. per 10 gallons 1 fl. oz. per 2 gallons
TOP UP DOSAGE need not be added every time the tank/boiler is filled, but preferably added during working periods. There is no advantage in using water treatment when the water is left open to the air for long periods.
150 ml. per 375 litres 100 ml. per 250 litres 50 ml. per 125 litres 10 ml. per 25 litres. |
|