Heatreat 502

Heatreat 502 is a blended formulation of tannins, alkalis and polymers for preventing corrosion, scaling and organic fouling in hat water and chilled water systems.

Appearance                        Dark Brown Fluid

ph as Supplied                    9.7

Specific Gravity                  1.14

 

Treatment for steam boilers Heatreat 502 is dosed so as to maintain the D.M. value (tannin index) and the ph of the boiler water within set limits.

Usually the D.M. value of 12 - 16 and a ph greater than 10

For D.M. value a simple test using reagents in tablet form is available.

For ph, indicator test papers are suitable.

 

Dosage Requirements

The initial dose is normally 3litre/1 cubic metre

 

Metric measurements

3 litres per 1000 litres                            1 litre per 333 litres

500ml per 167 litres                               100 ml per 33 litres

10 ml per 3.3 litres                                 1 ml per 330 ml

 

Imperial measurements

24 pints per 1000 gallons                      12 pints per 500 gallons

6 pints per 250 gallons                           3 pints per 125 gallons

1 pint per 40 gallons                               10 fl. oz. per 20 gallons

5 fl. oz. per 10 gallons                            1 fl. oz. per 2 gallons

 

TOP UP DOSAGE need not be added every time the tank/boiler is filled, but preferably added during working periods. There is no advantage in using water treatment when the water is left open to the air for long periods.

 

150 ml. per 375 litres                            100 ml. per 250 litres

50 ml. per 125 litres                               10 ml. per 25 litres.

 